MTS Metallurgical Testing Services | |
Download the PDF: Square core drilled spigots load test (3998 downloads ) |
Test Report
To | Sorrento Glass | Report No | MTS-18448 SG | ||
1 / 7 Hector St Osborne Park WA 6017 | Issue Date | 21/07/2014 | |||
Order No. | G. Vile | Test Date | 13/06/2014 |
Introduction
MTS Metallurgical Testing Services was engaged to perform load tests on a toughened glass pool fence panel in general accordance
with the requirements of AS 1926.1 – 2012.
Details
ID | Item/Heat No. | Dimensions/Type/Details | Finish | Overall Assessment |
---|---|---|---|---|
18448/01 | Frameless Glass | 1.0m Long x 1.2m High with 44mm Coredrilled Square Duplex stainless steel spigots |
Polished | COMPLIES |
Examinations & Tests
A visit was made to the test site to verify the installation arrangements against supplied drawings. A subsequent visit was made once the
grout had cured to conduct a load test.
Summary
The results of the tests reported herein COMPLIED with the requirements of the stated standard/s and/or specification/s.
Colin Lorrimar
Metallurgical Testing Manager
RESULTS
Visual Examination
The panel was installed in accordance with this drawing, modified to suit the 100mm thick floor at the test site.
Core-Drilled Spigots
44mm Square Spigot – Face view | 44mm Square Spigot – Side view |
Load Test
Test Specification | AS 1926.1 – 2012, Appendix C | Test Procedure | MTS-TP3.7 Load Tests of Protective Enclosures,Barriers and Fences |
Specimen ID | Test Load (N) | Deflection Under Load (mm) | Permanent Distortion (mm) | Observations | Assessment |
---|---|---|---|---|---|
18448/01 | 330 | 24 | 1.5 | No damage, loosening or permanent distortion | COMPLIES |
The pool fence panel under test load showing the hydraulic ram and digital load indicator.
Requirements: No breakage or signs of fracture or loosening of any part. Maximum Permanent Distortion: 6mm.
MTS-18448 SG This document shall not be reproduced, except in full.